Why does my manual say 40001 when the tool wants 0?

Home › Forums › Industrial Automation › Why does my manual say 40001 when the tool wants 0?

  • This topic is empty.
Viewing 1 post (of 1 total)
  • Author
    Posts
  • #2554
    惠源
    Keymaster

    [OFFICIAL POST] EEDIY Team (official)

    The Modbus spec numbers items from 1, but the message on the wire counts from 0. Many manuals write holding registers as “4xxxx” (40001 = register 1, sent as 0). That is a vendor habit, not part of the spec.

    Fix: if your values look shifted by one, try the address minus 1.

    Sources:

    EEDIY Team (official)

Viewing 1 post (of 1 total)
  • You must be logged in to reply to this topic.